LFE10火焰監(jiān)測器
品牌:SIEMENS(西門子)(原LANDIS&GYR)
產(chǎn)地:德國
LFE10和LAE10都為配合西門子專用火焰探測器使用的火焰檢測器。
-
LFE10可以與SIEMENS西門子公司的QRA...系列火焰探測器或者離子探針配合使用,把模擬量電流信號轉(zhuǎn)換為開關(guān)量信號,并輸出給燃燒器程控器。
-
LAE10可以與SIEMENS西門子公司的RAR...系列燃油火焰探測器配合使用,把模擬量電流信號轉(zhuǎn)換為開關(guān)量信號,并輸出給燃燒器程控器。
-
此兩款火焰檢測器必須每24小時停止工作一次。如需要24小時連續(xù)工作,請選用LFE50系列產(chǎn)品。
Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit, etc. - at least one controlled shutdown is required every 24 hours. The LFE10 is suited for the supervision of gas flames and luminous or blue-burning oil flames in connection with UV detectors QRA... or a flame rectification probe.
Flame safeguards are used primarily in conjunction with the LEC1 burner control on the following applications:
-
Dual-supervision of burners: Supervision of the main flame or of the pilot and main flame by two identical or different types of flame detectors
-
Supervision of forced draught oil / gas burners: Supervision of the flame with different types of detectors, depending on the operating mode
-
Multi-flame supervision: Plants with several burners whose flames must be supervised individually by one or several detectors, whose startup and supervision, however, should or must be carried out centrally and simultaneously by only one burner control
-
The flame safeguards can also be used in connection with other types of burner controls provided the given combination and selected circuitry do not impair the burner control’s safety functions
-
The flame safeguards are also used as flame indication units in combustion plant with manual startup
|
主要參數(shù)
|
|
主電壓
|
AC220V -15%...AC240V +10%
|
|
AC100V -15%...AC110V +10%
|
|
主頻率
|
50...60Hz ±6%
|
|
外部保險絲
|
10A
|
|
功率
|
4.5VA
|
|
端口額定電流
|
2A
|
|
保護等級
|
IP40
|
|
重量(不含底座)
|
395g
|
|
|
環(huán)境條件
|
|
運輸環(huán)境
|
IEC 60 721-3-2
|
|
內(nèi)部條件
|
class 2K2
|
|
機械條件
|
class 2M2
|
|
溫度范圍
|
-20...+60oC
|
|
濕度
|
<95%
|
|
運行環(huán)境
|
IEC 60 721-3-3
|
|
內(nèi)部條件
|
class 3K5
|
|
機械條件
|
class 3M2
|
|
溫度范圍
|
-20...+60oC
|
|
濕度
|
<95%
|
|
不得進水
|
|
|
電路圖1 - 2臺LAE10連接RAR火焰探測器,與LEC1燃燒器控制器連接
|
|